1Ø -Digital Current Protection Relay [900CPR-1-230V]
Measuring Parameter | Under Current, Over Current Protection for 1Ø System |
Electrical Connection | 1Ø-2W |
Display | 3 Digit Liquid Crystal Display |
CT Setting | CT Primary: 1A/5A – 999A, CT Secondary: 1A/5A (selectable) |
Time Ranges | Power ON Delay: 0.5 – 99.9s,Trip Time Delay: 0 – 99.9s Recovery Time Delay: 0 – 99.9s, Response Time: < 200ms |
Accuracy | Current: ±1% of setting ± 2 digit, Time Setting Accuracy: ±5% of setting ± 100ms |
Output Contact | 1 C/O (SPDT) |
Output Rating | NO: 5A, 250V AC, NC: 3A, 250V AC |
Supply Voltage | 230V AC ±15% |
Size | 35 mm |
Mounting Type | DIN Rail Mount |

1Ø-Digital Current Protection Relay, Auxillary Supply [900CPR-1-BL-U]
Measuring Parameter | Under Current & Over Current |
Electrical Connection | 1Ø-2W |
Display | 3 Digits Liquid Crystal Display With Backlight |
CT Setting | CT Primary: 1A / 5A – 999A, CT Secondary: 1A / 5A (selectable) |
Time Ranges | Power ON Delay: 0.5–99.9sec, Trip Time Delay: 0–99.9sec, Recovery Time Delay: 0–99.9sec (In Auto Reset Mode), Response Time: <200ms |
Accuracy | Current: ±1% of Setting ± 2 digits, Time Setting Accuracy: ±5% of Setting ± 200ms |
Output Contact | 2 X 1 C/O (SPDT) |
Output Rating | NO: 5A@250V AC, NC: 3A@250V AC |
Supply Voltage | 85 to 270V AC / DC |
Size | 35mm |
Certification | CE |
APPLICATIONS
- Monitoring of Lighting Systems
- Heating Circuits
- Machine Control